Hydrant and cannon integrated fire monitor

  • type:PS/SSFT
  • model:Fire cannon
  • Introduction: It is widely used in storage and process plant of material, semi-product, end product in chemical enterprise for methyl alcohol, chlor-alkali, organosilicone, oil refining, rubber, etc., also can be used in cold area in north.
    栓炮一体式消防炮
    Hydrant and cannon integrated fire monitor

    该产品是消防炮和地上消火栓(快开调压、防冻防撞)的组合装置。其特点是即有消防炮的功能,又有地上消火栓的快开调压、防冻防撞功能,既可以使用消防炮进行远距离大范围的灭火作业,也可以使用消防栓的两个KWS型快速接口连接水带、水枪等喷射设备进行近距离、小范围的辅助灭火作业。该产品被广泛应用于甲醇、氯碱、有机硅、炼油、橡胶等化工企业的原料、成品、半成品的储罐区和工艺装置区,更可放心的用于北方寒冷地区。
    This product is integrated device of fire monitor and post fire hydrant (quick-opening pressure-regualting, antis-freezing and anti-collision). The feature is it has the function of both fire monitor and post fire hydrant, it can put out fire in long distance and wide area, and can put out fire in short distance, small area by two KWS quick connection to connect with spray device like water hose, water gun, etc. It is widely used in storage and process plant of material, semi-product, end product in chemical enterprise for methyl alcohol, chlor-alkali, organosilicone, oil refining, rubber, etc., also can be used in cold area in north.
    主要参数:
    Main parameters

    型号 Model PS50/SSFT100/65-1.6 PS60/SSFT150/80-1.6
    消防炮进口 Gun head nominal diameter(DN) 80 100
    消火栓公称通径Fire hydrant nominal diameter(DN) 100 150
    公称压力 Nominal pressure(Mpa) 1.6 1.6
    工作压力范围 Working pressute range(Mpa) 0.8~1.0 0.8~1.0
    公称流量 Nominal flow(LS) 50±8% 60±6%
    射程 Range(m) ≥65 ≥70
    俯仰角 Pitching angle -50°~+70°
    水平回转角 Level rotation angle 0~360°
    炮嘴喷雾角 Cannon mouth spray angle ≥90°
    出水接口型号x数量 Cannon mouth spray angle KWS65×2 KWS80×2
    吸水接口规格 suction interface specification M125×6 M170×6
    配对法兰规格 paired of flanges specifications PN1.6/DN100 PN1.6/DN150
    配对法兰标准 mating flange standard HG20593-1997
    地下埋深高度 underground depth 按当地防冻层深度确定(Dependent upon depth of the local frost layer)
     
     
    This product is integrated device of fire monitor and post fire hydrant (quick-opening pressure-regualting, antis-freezing and anti-collision). The feature is it has the function of both fire monitor and post fire hydrant, it can put out fire in long distance and wide area, and can put out fire in short distance, small area by two KWS quick connection to connect with spray device like water hose, water gun, etc.